MENU
BUY PARTS
REQUEST QUOTE
FIND LOCATION
back
to top
Back to listing page

3512B (CTL)

Diesel Generator Sets

The C32 with the upgradeable packaging design has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance to matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.

Show
Minimum Rating 1230 ekW
Maximum Rating 1500 ekW
Voltage 220 to 13800 Volts
Frequency 60 Hz

Availability Contact Dealer

FEATURES & BENEFITS

Cat Diesel Engine

Cat Diesel EngineReliable, rugged, durable designField-proven in thousands of applications worldwideFour-stroke-cycle diesel engine combines consistent performance and ex... Read more

Generator

GeneratorMatched to the performance and output characteristics of Cat engines Industry leading mechanical and electrical design Industry leading motor starting capabiliti... Read more

EMCP Control Panel

EMCP Control PanelThe EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform design... Read more

Design Criteria

Design CriteriaThe generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response. Read more

UL 2200 / CSA - Optional

UL 2200 / CSA - OptionalUL 2200 listed packages CSA CertifiedCertain restrictions may apply. Consult with your Cat® Dealer. Read more

Single-Source Supplier

Single-Source SupplierFully prototype tested with certified torsional vibration analysis available Read more

World Wide Product Support

World Wide Product SupportCat Dealers provide extensive post sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores op... Read more

SPECIFICATIONS FOR 3512B (CTL)

Collapse All
Generator Set Specifications
Minimum Rating 1230 ekW
Maximum Rating 1500 ekW
Voltage 220 to 13800 Volts
Frequency 60 Hz
Speed 1800 rpm
Emissions/Fuel Strategy Tier 2
Engine Specifications
Engine Model 3512C ATAAC, V-12, 4-Stroke Water-Cooled Diesel
Compression Ratio 14.7:1
Aspiration TA
Governor Type Adem?3
Fuel System Electronic unit injection
Stroke 190 mm
Bore 170 mm
Displacement 51.8 l

SELECT MODELS TO COMPARE

Diesel Generator Sets

C7.1 (60 Hz)

Maximum Rating 175 ekW
Minimum Rating 120 ekW
Emissions/Fuel Strategy Non Regulated
Voltage 208 to 480 Volts
Diesel Generator Sets

C15 (50 Hz) China Non Road

Maximum Rating 550 kVA
Minimum Rating 365 kVA
Emissions/Fuel Strategy Low Fuel, Tier 2 or 3
Voltage 208 to 600 Volts
Diesel Generator Sets

3512C (1750 ekW, 60 Hz)

Standby Rating 1750 ekW
Prime Power Rating 1600 ekW
Emissions/Fuel Strategy U.S. EPA Cert., Tier 2
Voltage 380 to 13800 Volts
Diesel Generator Sets

C7.1 | DE165E0

Minimum Rating 150 ekW
Maximum Rating 150 ekW
Emissions/Fuel Strategy Non Regulated
Voltage 240 to 480 Volts
Diesel Generator Sets

DE200 GC (50 Hz)

Maximum Rating 200 kVA
Minimum Rating 200 kVA
Emissions/Fuel Strategy Non Regulated
Voltage 380 to 415 Volts
Diesel Generator Sets

C4.4 (60 Hz)

Maximum Rating 60 ekW
Minimum Rating 36 ekW
Emissions/Fuel Strategy U.S. EPA Cert., Tier 3
Voltage 208 to 600 Volts
Diesel Generator Sets

C15 | 500 kVA (50 Hz)

Maximum Rating 500 kVA
Minimum Rating 500 kVA
Emissions/Fuel Strategy India CPCB/MoEF
Voltage 415 Volts
Diesel Generator Sets

3612 (50 Hz)

Maximum Rating 4850 kVA
Minimum Rating 4400 kVA
Emissions/Fuel Strategy Low Fuel Consumption
Frequency 50 Hz
of
01
SEND REQUEST

Select your equipment and fill out your contact information

02
GET A QUOTE

A sales rep will send you an official quote and other related information

03
PAYMENT & DELIVERY

Payment – Lead time - Delivery

Select Up to
3 Models to Compare
Model 1
Model 2
Model 3