3512B (CTL)

Diesel Generator Sets

The C32 with the upgradeable packaging design has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance to matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.

Show
Minimum Rating 1230 ekW
Maximum Rating 1500 ekW
Voltage 220 to 13800 Volts
Frequency 60 Hz

Availability Contact Dealer

FEATURES & BENEFITS

Cat Diesel Engine

Cat Diesel EngineReliable, rugged, durable designField-proven in thousands of applications worldwideFour-stroke-cycle diesel engine combines consistent performance and ex... Read more

Generator

GeneratorMatched to the performance and output characteristics of Cat engines Industry leading mechanical and electrical design Industry leading motor starting capabiliti... Read more

EMCP Control Panel

EMCP Control PanelThe EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform design... Read more

Design Criteria

Design CriteriaThe generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response. Read more

UL 2200 / CSA - Optional

UL 2200 / CSA - OptionalUL 2200 listed packages CSA CertifiedCertain restrictions may apply. Consult with your Cat® Dealer. Read more

Single-Source Supplier

Single-Source SupplierFully prototype tested with certified torsional vibration analysis available Read more

World Wide Product Support

World Wide Product SupportCat Dealers provide extensive post sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores op... Read more

SPECIFICATIONS FOR 3512B (CTL)

Collapse All
Generator Set Specifications
Minimum Rating 1230 ekW
Maximum Rating 1500 ekW
Voltage 220 to 13800 Volts
Frequency 60 Hz
Speed 1800 rpm
Emissions/Fuel Strategy Tier 2
Engine Specifications
Engine Model 3512C ATAAC, V-12, 4-Stroke Water-Cooled Diesel
Compression Ratio 14.7:1
Aspiration TA
Governor Type Adem?3
Fuel System Electronic unit injection
Stroke 190 mm
Bore 170 mm
Displacement 51.8 l

SELECT MODELS TO COMPARE

Diesel Generator Sets

C3.3 | DE56AE0

Maximum Rating 49.2 kVA
Minimum Rating 45.0 kVA
Emissions/Fuel Strategy Non-Certified Emissions
Voltage 220 to 380 Volts
Diesel Generator Sets

C13 (60 Hz)

Maximum Rating 400 ekW
Minimum Rating 320 ekW
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 380 to 415 Volts
Diesel Generator Sets

3512B

Minimum Rating 1230 ekW (1320 kVA)
Maximum Rating 1500 ekW (1875 kVA)
Voltage 220 to 13800 Volts
Frequency 50 or 60 Hz
Diesel Generator Sets

DE1100 GC

Maximum Rating 1100 kVA
Minimum Rating 1100 kVA
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 400 - 415 Volts
Diesel Generator Sets

C3.3 (60 Hz)

Maximum Rating 60.0 ekW
Minimum Rating 27.0 ekW
Emissions/Fuel Strategy EU Stage II & R96/EUIIIa
Voltage 110 to 480 Volts
Diesel Generator Sets

C9 (60 Hz)

Maximum Rating 300 ekW
Minimum Rating 180 ekW
Emissions/Fuel Strategy EU Stage IIIA, Low Fuel
Voltage 220 to 480 Volts
Diesel Generator Sets

DE660 GC (50 Hz)

Maximum Rating 660 kVA
Minimum Rating 660 kVA
Emissions/Fuel Strategy Non Regulated
Voltage 380 to 415 Volts
Diesel Generator Sets

C7.1 (50 Hz)

Maximum Rating 220 kVA
Minimum Rating 135 kVA
Emissions/Fuel Strategy Non Regulated, EU Stage IIIA
Voltage 110 to 480 Volts
of